SF6 Leak Detection
The latest developments in this task are that preparations are underway for leak detection from UAVs. This work builds on the completed research at ground level and at different temperatures and distances.
SF6 Alternatives
Research is progressing on laboratory testing of alternatives. Updates are in two EPRI laboratories – one looking at the gas handling and one looking at the new gas circuit breaker technologies.
Guidebook Development
The research tasks conducted each year allow for the continued expansion of the GIS and GIL guidebook. Follow the link for more information
1 - SF6 Leak detection
SF6 leak detection is important due to the increasing pressure to reduce SF6 emissions. EPRI has completed extensive testing with cameras at ground level (see EPRI report 3002024618 chapters 6 and 7). From that research there were many learnings. One of those learnings is highlighted below. It demonstrates the large role the background plays in SF6 leak detection using infrared-based technologies. A sky background significantly increases the sensitivity of the detection. With that sky background removed, it can be seen in the image below that the exact same leak is made indetectable.
Looking forward, the current research is building on that past research to address the important question on how to detect SF6 leaks at high elevations without the need for an outage or ladders or scaffolding. To achieve this, research is exploring how effectively SF6 leak detection can be performed from a UAV. In August this year tests will be conducted in the energized EPRI research substation using controlled SF6 leaks. An example of a controlled leak is shown below.
This controlled leak will be placed in the substation in the location shown below. The research will be examining the ability of the UAV-mounted camera to detect leaks at various distances – and whether there is strong influence from the wind produced by the UAV rotors and whether the UAV platform is stable enough to perform the necessary frame subtractions.
2 - SF6 Alternatives
To answer the wide range of questions related to new alternatives to SF6 (vacuum and Fluoronitrile solutions) research is underway in two EPRI laboratories. The first laboratory in Charlotte, NC is researching the following aspects related to Fluoronitrile SF6 Alternatives:
Handling
Analysis
Recycling
Disposal
A close-up view of the Charlotte, NC laboratory is shown below.
The second laboratory is in Lenox, MA and is being modified to allow for the deployment and evaluation of new SF6-free breaker technologies. The research will allow for a deeper understanding of the breaker performance before deployment in a substation serving customer load. Utilities are accelerating the progress the supplemental funding to support the deployment of breakers.
3 - Guidebook Development
GIS Map of the on-line GIS Monitors under evaluation
Arc Flash
Burndown of bare and covered conductors
Flammability of equipment under fault condition
Damage to crossarms and insulators under fault conditions
Performance of sensors during faults
Grounding and stray voltages; step and touch voltages during faults
Evaluation of vegetation faults
Fuse cutout and single-phase recloser performance
Conductor slap
OEM: Power Diagnostix
Details
Portable partial discharge detection utilizing UHF and AE
OEM: Doble
Details
Portable partial discharge detection utilizing UHF and AE UHF608 converter
OEM: Omicron
Details
PC controlled multi-purpose partial discharge detection system which can be configured to detect UHF when utilizing a UHF608 converter
PC controlled multi-purpose partial discharge detection system which can be configured to detect UHF
Details
The EPRI RF Monitor is battery powered and sends data wirelessly to a base station. The AE signals detect partial discharges or moving particles
Details
The EPRI RF Monitor is battery powered and sends data wirelessly to a base station. The UHF signals detect electrical partial discharge signals via UHF couplers fitted to the GIS
The GIS in green is being adapted for research on SF6-Alternative mixtures. Research topics include commissioning, handling, safety, recycling and disposal
The GIS in orange has SF6 as the dielectric and serves as our benchmark for the studies on SF and SF6 Alternatives
Hover over these links to locate a monitor or view more information on research:
AIA Compact
| DFA 300
| MPD System using a UHF608
| QCM-PPDM
| PD-Smart
| EPRI RF Monitor - AE
| EPRI RF Monitor - UHF
| GIS for SF6 Alternatives
| GIS for SF6 research
The current guidebook version is the EPRI product ID 3002024618. It covers the important topics of condition monitoring and SF6 leak detection. In 2023 it is being expanded to include the new research this year on expanding the EPRI RF Monitoring Suite to include GIS and GIL monitoring. Monitoring is focused on three areas:
AE (Acoustic Emission) monitoring for partial discharge detection
SF6 Density monitoring for early detection of leaks
Tank temperature monitoring for early detection of internal overheating
An example of an AE (Acoustic Emission) monitor on the GIS in the EPRI laboratory is shown below. In 2023 the sensitivity and internal signal processing of this approach continues to be improved.
In parallel research is underway on using EPRI RF Monitors to detect PD in GIS and GIL via high frequency currents in the ground straps. Below is an image of some recent tests that have demonstrated early success with the approach – as seen in the response from the monitor seen below when excited by a standards-based PD generator. In the months ahead the detection will be optimized and then proven with field trials.