Research & Technical Content
Calculators
Conductor Rating Calculator (CRC)
This calculator provides a tool for planners, designers, and operators to first determine the temperature of an overhead line conductor to meet their transmission requirements. The user inputs conductor and ambient conditions information and, using IEEE Standard 738-2012, the calculator can determine the:
-
Steady-State Thermal Rating - Given the conductor temperature and the steady-state weather parameters, the heat losses due to convection and radiation, the solar heat gain and the conductor resistance can be calculated. The corresponding conductor current that produced this conductor temperature under these weather conditions can be found. The steady-state and transient thermal ratings calculations can be performed for a range of target conductor temperatures.
-
Steady-State Current Rating - Given a conductor current and steady-state weather parameters, the conductor temperature produced by that current can be determined. This is done by estimating a conductor temperature and performing the steady-state thermal rating calculation. Then adjusting the estimated temperature up or down until the calculated thermal rating current equals the given current. The steady-state and transient conductor temperature calculations can be performed for a range of step currents.
High Temperature Conductor (HTC) Matrix Calculator
The HTC Matrix Calculator is a web-based application that gives the user the ability to calculate the following:
-
Aluminum Annealing : calculates an estimate of the remaining strength of a conductor after exposure to extended periods of high temperature operations.
-
High Temperature Creep: determines the effect of specified high-temprature on creep and ultimately span sag.
-
Compression Conductor Calculations: calculate the Ultimate Tensile Strength (UTS) of a single-stage compression connector for Drake ACSR conductor after it has been exposed to the prescribed temperatures (above) for prescribed lengths of time (above).
Research Results Summaries
High Temperature Operation of Polymer Insulators
This is a research summary of testing that involved exposing polymer transmission line insulators. The objective was to determine the thermal risks to asset life from high temperature operation. The testing was conducted at the EPRI Lenox Lab, and a full report is available for download.
Effect of High Temperature on Tensile Strength of Aluminum 1350-H19
This attachment provides a list of pertinent standards associated with operating overhead transmission lines at elevated temperatures.
Reference Information
High Temperature Operations Standards
This attachment provides a list of pertinent standards associated with operating overhead transmission lines at elevated temperatures.